Helical piles and anchors are widely used in foundation construction due to their efficiency, versatility, and performance. However, specifying them correctly is critical to ensuring both structural reliability and cost-effectiveness.
When specifying helical piles, designers generally choose between two main approaches:
Ultimate resistance is the maximum load a helical pile can support before failure. Engineers apply a factor of safety or resistance factors to the ultimate resistance to ensure performance under normal service conditions. Best practice is to design the ultimate resistance to be limited by the geotechnical capacity, not the structural strength.
There are two methodologies used to evaluate pile performance:
Typical standards include a factor of safety of 2.0 for permanent applications using the ASD methodology. Tieback anchors tested with proof loads may use a lower factor of safety of 1.5 by the ASD standard. LRFD resistance factors range from 0.65–0.75 in compression and 0.55–0.65 in tension.

Torque can be used as an indirect measure of capacity. The specified torque should be based on the required minimum capacity (ultimate resistance). For tested helical piles and tieback anchors, proof testing governs acceptance. Pre-production testing is also used to confirm site specific torque correlation (Kt) factors. It is very important to use the appropriate torque correlation factor when specifying installation torque. The pile manufacturer, shaft type, shaft size, and overall pile length need to be considered.
The relationship between installation torque and ultimate capacity is expressed using a simple formula. A torque factor, Kt, is used as a multiplier and is based on the type and size of the helical pile shaft.
The torque factor is inversely related to shaft size—the larger the shaft, the smaller the Kt value. Chance square shaft helical piles, have the largest torque factor, meaning they can support the most axial capacity with the least amount of torque.
Qult = Kt x T
Where:
Qult = Ultimate Capacity [lb (kN)]
Kt = Empirical Torque Factor [ft-1 (m-1)]
T = Installation Torque, [ft-lb (kN-m)]
Accurate torque correlation (Kt factor) requires proper installation conditions, including sufficient advancement rate and appropriate Kt values. It is strongly recommended to only specify helical piles manufactured by suppliers who have published pre-qualified torque correlation factors.
To obtain the Chance torque correlation factor by product, download the Chance Technical Design Manual.
Capacity is often based on the average torque over the final 3 feet of installation, where soil interaction at the bearing depth is most critical. This is true for both compression and uplift resistance.
Penetration into dense soil may require higher-strength helical pile shafts due to increasing torque during installation. Using HeliCAP helical capacity design software, the capacity of a pile can be configured for a user-input soil profile. The software, free to use on any web-connected device, will provide capacity data of selected piles.
Create an account to start using HeliCAP.

Proper specification of helical piles requires clear communication, appropriate safety factors, and correct use of torque correlations to ensure safe and economical designs. Whether the specification is based on minimum capacity, installation torque, or a combination of both, it should define the load basis, safety or resistance factors, torque correlation assumptions, testing requirements, and final acceptance criteria.
If you need help with a helical pile design, reach out to your local distributor for expert engineering assistance.
CHANCE® Foundation Solutions recently wrote a blog post arguing why you should use at least 2 me...
Learn how Geotechnical Engineers use valuable jobsite data to validate their recommendations for de...
Helical pile installers and designers get this question all the time: “Do I need to do full scale l...
The two questions every helical pile engineer should ask when starting a new project are: What are...
The CHANCE wireless torque indicator, manufactured by Hubbell Power Systems, is a state-of-the-art...
This is an in depth explanation, through an example project, of how an engineer or contractor can u...
When it comes to deep foundations and high capacity piles in general, helical piles are often overl...
Gary Seider, Engineering Manager at Hubbell Power Systems, recently posted an interesting story on...
Helical piles are a proven deep foundation solution used across commercial, industrial, utility, and...
Looking for more information? Fill in the form and we will contact CHANCE Foundation Solutions for you.